- اسم العلامة التجاريةTrotec
Devatech- Steam Humidifier
AC4 Centrifugal Atomizing Humidifier
The centrifugal AC4 humidifier is operating with adia-batic effect: it transforms water into a very fine mist which is immediately absorbed by the air. This method allows to humidify and cool at the same time.
It can be easily installed both on the wall and on the ground. All these features, with simple and robust construc-tion, make this humidifier ideal for a variety of applications
Specifications |
|
Dimension |
310x310x480 mm |
Weight |
7Kg |
Power supply |
230V/50Hz |
Power consumption |
70W |
Humidity capacity |
Up to 4,5l/h |
Coverage |
100-150m² |
Colour |
White |
Instructions
Maximum permissible water pressure in Pascal : 0,5MPa
**Caution**
If the supply cord is damaged, it must be replaced by the manufacturer or a similarly qualified personne in or-der to avoid a hazard.
Device to unplug before intervening.
**Water connection**
Place the unit on a level surface, such a benchtop or floor. In an environnment with little to no ventilation, place the unit in a central location. In a ventilated area, place unit near the intake end. Then, connect a water supply to female 6mm inlet.
**Power connection**
Plug the unit directly into an electrical outlet for evaluation. Listen for a smooth, quiet operation. Motor shaft should be centered and vertical. Make any necessary adjustments. After evaluation, connect AC4 to desired control device as you see options below;
Plug into a Sensor for a best automatic control
Plug into a timer for a specific automatic control intervals
**Operation**
WARNING: Designed for atomizing water only!!! Don’t use flammable, toxic or corrosive liquids.
Operating the unit using the fogging head will provide directionnal fogging output and a drier fog.
For a maximum fogging and circulation, operate unit without the lower housing as well as upper housing and fogging head. Fog will propel from 1,2 to 1,5 feet above unit.
**Troubleshooting**
*No Fog*
Check for motor rotation. If motor is operating properly, check for an adequat amount of water in the pan (1/4’’ to 1 1/4’’). If the pan runs dry, the float valve may be sticking in the up position. If so, the inlet water pressure needs be sticking in the up position. If so, the inlet water pressure needs to be reduced. If water supply is adequat, check the ta-pered pump for internal calcium build-up. Remove, inspect and clean as needed.
*Overflowing Pan*
An overfilled pan can cause poor quality of fog and wetness around the unit. A leaky float valve or a float that has filled with water may be the problem. To check the float, raise it out of the water and visually inspect it. No water should be inside and it should not sink. If OK, then check for leaky valve. Turn water off and remove the fogger from the pan. Empty the pan and towel dry. Hold the float in the up position and turn water enters the pan while the float is in the up position, the float valve needs to be replaced.
**Maintenance**
Check and clean Atomizing Screen and filter
Regularly clean the reservoir pan assembly with soap and water to remove dirt and sediment. Use liquide bleach after cleaning to sterilize any parts.
Periodically remove strainer screen and thoroughly flush. Also check to make sure the Pump assembly is free of debris.
Once every three months, check units for calcium build-up. If build-up deposits are present, disconnect the water and take the unit outside. Pour calcium dissolving solvent (available in local hardware stores) in pan and operate unit outside to soften and remove the deposits.
About once a year, remove the housing to check the SST Atomizing Screen to be sure the slots are clear of mine-ral build-up. To clean, scrub with calcium dissolving solvent.