DESICCANT DEHUMIDIFIER TTR 400 D
The TTR 400 D desiccant dehumidifier not only impresses with its very good dehumidification performance even at low dew points well below 0 °C but also with maximum versatility due to the TTR Trisorp Dual principle of operation:
Two separate air flows for dry and regeneration air with two separate fans for each circuit allow an efficient pressure-tolerant recirculation when setting up the dehumidifier outside as well as inside the room to be treated.
A few practical benefits:
- Professional quality „made in Germany“ Originally produced by Trotec
- Duoventic air volume regulation: Advanced control electronics allow a stepless, separate adjustment of the moisture content and volume flow of the required dry air.
- TTR Trisorp Dual principle of operation with two separate air circuits for pressure-tolerant recirculation mode for power-saving dehumidification at an increased drying rate
- Up to 30 % lighter than competitive models with the same performance
- Maximum of performance with minimum of dimensions and weight
- Extremely low in maintenance
- Stackable to save space
- Tried and tested German industrial design – protected prototype
- Technical dataEquipment, features and functions
TECHNICAL DATA
General information
Article number 1.110.000.021
Dry air (in case of intake air 20 °C / 60 % RH)
Dehumidification [kg/24h] 38,4
Dehumidification [kg/h] 1,6
- air volume [m³/h] 130
- air volume [m³/h] 450
Nominal air volume [m³/h] 350
External compression [Pa] 200
Connection inlet Ø [mm] 125
Connection outlet Ø [mm] 125
Regeneration air
Nominal air volume [m³/h] 65
External compression [Pa] 80
Connection inlet Ø [mm] 80
Connection outlet Ø [mm] 80
Operating principle
Designation TTR-Trisorp-Dual
Operating range
Temperature min. [°C] -15
Temperature max. [°C] +35
Humidity min. [% RH] 0
Humidity max. [% RH] 100
Electrical values
Input voltage [V] 230
Frequency [Hz] 50/60
Nominal current consumption [A] 7,2
Power input heating [kW] 1,95
Power input [kW] 2,2
Recommended fusing [A] 16